CTE-6001

CTE-6001

Tstat: High Limit, Manual Reset, SPST


The KMC CTE-6001 is a pushbutton manual reset high limit control (firestat). It is designed for installation in supply air ducts to shut down heating/air conditioning equipment or ventilating fans when the duct air temperature exceeds a preset limit. The “cut-out” temperature setpoint is field adjustable in a range of 100°F to 250°F (38°C to 121°C). Once set, the tem­per­a­ture setpoint can be “locked in place” by tightening the screw in the setpoint lever. This device is shipped with the “cut-out” temperature preset at 135°F (57°C). It can be man­u­al­ly reset without removing the cover. The helix bimetal sens­ing element is protected from damage by a rigid outer shield. The insertion length is 7-1/2 inches (191 mm). Application The CTE-6001 Limit Control is intended for use in return air ducts to shut down heating/air conditioning equipment or ventilating fans when the duct air temperature exceeds a preset limit.